70 ECOM0010 - User manual
Pv
Comand Spv
Alarm Spv
O
On On
Hysteresis
parameter
$+< > 0
Time
Alarm
output
Comand Spv
Comand Spv
Comand Spv
Comand Spv
Alarm Spv
Alarm Spv
Value of alarm setpoint less
than 0and hysteresis value
greater than 0(Par.20
D+<
> 0).
N.B.: With hysteresis less
than “0 (
D+<
< 0) dotted
line moves under the alarm
setpoint.
10 Error ags
If the system shows malfunctions, the controller switches o
the control output and reports the error  ags on word 1009.
For example, the controller will report a defective
thermocouple by ashing alternately red/yellow LED and
setting to 1 the bit 0 of the word 1009.
For other signals see table below:
Cause What to do
BIT2
Error programming the
EEPROM
Call assistance
BIT0
Cold junction sensor
failure or room
temperature OFF the
limits
Call assistance
BIT3
Incorrect con guration
data. Possible loss of
calibration values
Check that con guration
parameters are correct
BIT1
Broken thermocouple
or temperature OFF the
limits
Check the connection
with the sensors and their
integrity
BIT4 Missing calibration Call assistance